REPLACING A FIREWALL PAIR:
A DATA DIODE AT THE IT/OT BOUNDARY

Summary →

A specialty manufacturer examined years of accumulated IT/OT firewall rules. The proposed architecture moves outbound historian and reporting data through a hardware-enforced one-way path, leaving only a small, documented set of flows on the firewall.

At a Glance →
ChallengeSolutionResult
A firewall pair at the IT/OT boundary carried 40-plus rules accumulated over nine years, with no one able to say which were still needed or who had requested them. Separated flows by direction, moved outbound reporting to a hardware-enforced data diode, and reduced the remaining firewall to a documented inbound rule set. Inbound path removed for reporting traffic; boundary rule count reduced from 40-plus to 6 in this illustrative scenario.

Client Profile

Sector: Specialty manufacturing, multi-line continuous process
Region: United States, single site
Environment: Approximately 900 OT assets, two historians, and a mix of current and unsupported Windows
Driver: Internal audit finding on boundary rule governance and a corporate requirement to evidence IT/OT separation
Engagement: Boundary assessment, architecture design, diode specification and commissioning support

Challenge →

The boundary worked. That was the problem. A firewall pair had sat between the enterprise network and the plant for nine years, and over that time every new reporting requirement, every integration project and every vendor connection had been solved by adding a rule. Nobody had ever removed one.

When internal audit asked for the business justification behind each rule, the plant could account for roughly a third of them. The rest had been requested by people who had since left, for systems that had since been decommissioned, or for projects nobody could name. The boundary had become a record of nine years of urgency rather than a security control.

Almost all legitimate traffic was outbound: historian extracts to the enterprise data lake, production reports to the business, and compliance evidence to a corporate system. Those flows needed no inbound path, yet a bidirectional firewall carried them.

The useful question was which rules existed only to let data out. That split a difficult governance problem into a focused architecture decision and a much smaller governance problem.

Approach →

The flow map, rather than the inherited rule set, became the design input. Outbound-only reporting could use a one-way path; necessary inbound and bidirectional flows remained on a smaller firewall policy.

01

Rule Archaeology and Flow Mapping

Every firewall rule was traced to a live flow or marked unexplained. Traffic was observed rather than inferred. Of the 40-plus rules, 11 carried observable traffic; four carried traffic that could not be attributed to a known system. More than 80 percent of observed volume was outbound historian and reporting traffic.

02

Splitting Flows by Direction

Outbound-only historian replication, reporting, compliance evidence and logs were separated from genuinely bidirectional integrations and inbound patch, signature and time synchronization flows. Each group was matched to the least capable mechanism that could serve it.

03

Diode Specification and Placement

A hardware-enforced one-way appliance was specified for outbound flows. The design accounted for historian protocol proxies, throughput at observed peak volume, sender behavior during receiver outages, and selective high availability for the historian stream.

04

Cutover and Firewall Reduction

The diode ran in parallel with the firewall path while both receiving streams were compared. Rules were then removed in groups with owners and rollback windows. A small documented rule set remained for patch distribution, time sync and necessary bidirectional integrations.

Results →

The outcome the plant valued most was that reporting flows no longer depended on a firewall configuration remaining correct. A hardware-enforced one-way appliance cannot be made bidirectional by a rule change.

MeasureBeforeAfter
Rules at the IT/OT boundary40+6
Rules with documented business justification~33%100%
Inbound path for reporting trafficPresentRemoved
Unexplained rules40
Boundary change requests per quarterRoutineNear zero
Audit finding statusOpenClosed
What Made It Work →

Observing traffic before designing. The rule set and reality had diverged; designing from the rules would have reproduced the problem in new hardware.

Splitting by direction first. This turned a large bidirectional boundary into a unidirectional path plus a smaller remainder.

Specifying high availability selectively. The business confirmed that the historian stream required it while reporting could tolerate delay.

Running both paths in parallel before withdrawal. Comparing completeness made it possible to remove rules the plant had been reluctant to touch.

What We Would Do Differently →

The protocol proxy work for the historian took longer than scoped because the historian version needed a poorly documented configuration. In a real engagement, the exact build and proxy behavior should be tested during specification rather than commissioning.

Do Your Boundary Rules Describe Your Traffic, or Your History?

Arista Cyber maps the flows before specifying anything. That often shows that much of a boundary exists to let data out, which can support a smaller and more defensible architecture than a firewall refresh.